Insulated Sheathed Control Cable
+
  • Insulated Sheathed Control Cable

Insulated Sheathed Control Cable

This product is manufactured according to GB/T9330-2008 "PVC insulated and PVC sheathed control cables with rated voltage of 450/750V and below".

Category:

Consultation:

Product Description

Product introduction

This product is manufactured according to the standard of GB/T9330-2008 "PVC insulated and PVC sheathed control cables with rated voltage of 450/750V and below".

Using properties

2.1 Rated voltage: U0/U is 450/750V

2.2 The allowable long-term maximum working temperature of the cable conductor is: PVC70℃, XLPE90℃;

2.3 The ambient temperature should not be lower than 0℃ when the cable is laid.

2.4 The allowable bending radius of the cable: for cables without armor and braided shielding, it should not be less than 6 times the outer diameter of the cable; for cables with armored or copper tape shielding structure, it should not be less than 12 times the outer diameter of the cable .

Model and name of the cable

Model Name     Name Scope of use
KVV Copper core PVC insulated PVC sheathed control cable Laying indoors, cable trenches, pipelines, bridges and other fixed occasions.
KYJV Copper core XLPE insulated PVC sheathed control cable
KVV22 Copper core PVC insulated PVC sheathed steel tape armored control cable Laying indoors, cable trenches, pipelines, direct burial and other fixed occasions that can withstand large mechanical external forces.
KYJV22 Copper core XLPE insulated PVC sheathed steel tape armored control cable
KVVP Copper core PVC insulated PE sheath braided shielded control cable Laying indoors, cable trenches, pipelines, bridges and other fixed occasions.
KYJVP Copper core XLPE insulated PE sheath braided shielded control cable
KVVP2 Copper core PVC insulated PE sheathed copper tape shielded control cable
KYJVP2 Copper core XLPE insulated PE sheathed copper tape shielded control cable
KVVR Copper core PVC insulated PVC sheathed flexible control cable Laying in occasions where softness is required for indoor movement
KYJVR Copper core XLPE insulated PVC sheathed flexible control cable
KVVRP Copper core PVC insulated PE sheath braided shield control flexible cable
KYJVRP Copper core XLPE insulated PE sheath braided shielding flexible control cable

Production scope

Model Rated voltage
(V )
Nominal section of conductor (mm2)
0.75 1.0 1.5 2.5 4 6 10
Number of cores
KVV,
KVVP
KYJV
KYJVP
450/750 2~61 2~14 2~10
KVVP2
KYJVP2
4~61 4~14 4~10
KVV22
KYJV22
450/750V 7~16 4~6 4~14 4~10
KVVR
KYJVR
4~61
KVVRP
KYJVRP
4~61 4~48

Note: The recommended core series are 2, 3, 4, 7, 8, 10, 12, 14, 16, 19, 24, 27, 30, 37, 44, 48, 52, 61 cores; Any non-standard specifications can also be produced upon request.

Main technical parameters of cables

Serial number Test conditions unit Cable rated voltage 450/750V
1 Finish voltage test    
1.1 Test length m Delivery Length
1.2 Test temperature   Ambient temperature
1.3 Test voltage V 3000
1.4 Hold time min 5
2 Insulated core voltage test    
2.1 Specimen length not less than m 5
2.2 Immersion time h 1
2.3 Water temperature 20±5
2.4 Test voltage    
2.4.1 Insulation thickness ≤0.6mm V 2000
2.4.2 Insulation thickness>0.6mm V 2500
2.5 Hold time min 5

 